*Cooling Capacity | 126 kW |
---|---|
**Heating capacity | 133 kW |
Power input | 42 kW |
Voltage | 400 V / 50 Hz / 3 Phases |
Operating current | 101 A |
Electrical connection | CEE125 A Socket |
*** Fuse protection | 125 A |
*** Cable recommendation | 5×35 mm² |
Flow rate | 21,6 m³/h |
Max. operating pressure | 6 bar |
External pressure head | 24 m |
Cold water connections | Storz B |
Capacity control | 2 Steps |
Refrigerant | R 32 |
Sound pressure at 5m | 57 dB(A) |
Transport weight | 1500 kg |
Dimensions (l x w x h) | 4000 x 1460 x 2100 mm |
*(**) Design conditions: | * Evaporator water temperatures 12/7°, Ambient temperature 35 °C |
*** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-130/WP/P - Air cooled chiller 126kW
Product information
Different requirements and applications on request.
Product description:
Air cooled corrosion resistant chiller with heat pump function for outdoor locations. This mechanical refrigeration unit for providing cold water is equipped with very quiet running scroll compressors. The liquid cooler has an integrated cold water pump head height of 24 m (240 kPa), it should be set up on a horizontal, stable work area and have at least 1 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
Heat exchangers | |
Buffer Tanks | |
Hoses / Fittings | |
Electric Accessories | |
Remote Monitoring |