| *Cooling Capacity | 1328 kW |
|---|---|
| Power input | 291 kW |
| Voltage | 400 V / 50 Hz / 3 Phases |
| Operating current | 559 A |
| Electrical connection | Cable terminals 3 Ph + PE |
| ** Fuse protection | 630 A |
| ** Cable recommendation | 7 x 150 (Single wire) mm² |
| Flow rate Evaporator | 229,0 m³/h |
| Flow rate Condenser | 306,5 m³/h |
| Max. operating pressure | 10 bar |
| Cold water connections | Victaulic 8" |
| Condenser water connections | Victaulic 6" |
| Capacity control | 12,5 – 100 % |
| Refrigerant | R134a |
| Sound pressure at 5m | 80 dB(A) |
| Transport weight | 5820 kg |
| Dimensions (l x w x h) | 4800 x 1500 x 2300 mm |
| * Design conditions: | Evaporator water temperatures 12/7°, Condenser water temperatures 30/35°C |
| ** Electrical protection: | On-Site power installation should be entrusted to an electrical specialist. |
| Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-1330-W - Water cooled chiller 1328kW
Product information
Different requirements and applications on request.
Product description:
The water-cooled fluid chiller for mechanical cold water-/fluid cooling, are equipped with two quiet running inverter screw compressors. The shell and tube evaporator and the shell and tube condenser consist of a steel shell fitted with copper tubes. The unit should be set up on a horizontal, stable work area inside and have at least 1.5 m free space on all sides and 4.5 m free space at the end of the unit. All controls and regulators are contained within the housing.
Accessories (optional)
![]() |
Dry Air Cooler / Cooling Tower |
![]() |
Pumps |
![]() |
Buffer Tanks |
![]() |
Hoses / Fittings |
![]() |
Electric Accessories |