| *Heating capacity | 242 kW |
|---|---|
| **Cooling Capacity | 181 kW |
| Power input | 46 / 56 kW |
| Voltage | 400 V / 50 Hz / 3 Phases |
| Operating current | 119 A |
| Electrical connection | CEE 125A Socket |
| *** Fuse protection | 125 A |
| *** Cable recommendation | 5×35 mm² |
| Flow rate Evaporator | 31,2 m³/h |
| Flow rate Condenser | 39,1 m³/h |
| Max. operating pressure | 10 bar |
| Cold water connections | Storz B |
| Condenser water connections | Storz B |
| Capacity control | 3 Steps |
| Sound pressure at 5m | 64 dB(A) |
| Transport weight | 950 kg |
| Dimensions (l x w x h) | 2432 x 928 x 1066 mm |
| *(**) Design conditions: | * Design conditions: Hot water temperatures 40°/45°C, evaporator water temperatures 15°C/10°C |
| *** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
| Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-180-W/WP - Heat pump water to water 242kW
Product information
Different requirements and applications on request.
Product description:
The water-cooled liquid chillers with reversible operation can be used for cooling/heating. The unit are equipped with two quiet running scroll compressors. The plate evaporator and the plate condenser consist of stainless steel. The unit should be set up on a horizontal, stable work area inside and have at least 1.5 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
![]() |
Dry Air Cooler / Cooling Tower |
![]() |
Pumps |
![]() |
Buffer Tanks |
![]() |
Hoses / Fittings |
![]() |
Electric Accessories |