*Heating capacity | 242 kW |
---|---|
**Cooling Capacity | 181 kW |
Power input | 46 / 56 kW |
Voltage | 400 V / 50 Hz / 3 Phases |
Operating current | 119 A |
Electrical connection | CEE 125A Socket |
*** Fuse protection | 125 A |
*** Cable recommendation | 5×35 mm² |
Flow rate Evaporator | 31,2 m³/h |
Flow rate Condenser | 39,1 m³/h |
Max. operating pressure | 10 bar |
Cold water connections | Storz B |
Condenser water connections | Storz B |
Capacity control | 3 Steps |
Sound pressure at 5m | 64 dB(A) |
Transport weight | 950 kg |
Dimensions (l x w x h) | 2432 x 928 x 1066 mm |
*(**) Design conditions: | * Design conditions: Hot water temperatures 40°/45°C, evaporator water temperatures 15°C/10°C |
*** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-180-W/WP - Heat pump water to water 242kW
Product information
Different requirements and applications on request.
Product description:
The water-cooled liquid chillers with reversible operation can be used for cooling/heating. The unit are equipped with two quiet running scroll compressors. The plate evaporator and the plate condenser consist of stainless steel. The unit should be set up on a horizontal, stable work area inside and have at least 1.5 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
Dry Air Cooler / Cooling Tower | |
Pumps | |
Buffer Tanks | |
Hoses / Fittings | |
Electric Accessories |