*Heating capacity | 213 kW |
---|---|
**Cooling Capacity | 193 kW |
Power input | 72 kW |
Voltage | 400 V / 50 Hz / 3 Phases |
Operating current | 163 A |
Electrical connection | 3 Ph + PE Cable terminals |
*** Fuse protection | 200 A |
*** Cable recommendation | 4×95 mm² (single wire) |
Max. flow rate | 33,2 m³/h |
Max. operating pressure | 6 bar |
External pressure head | 27 m |
Cold water connections | Storz B |
Capacity control | 2 Steps |
Refrigerant | R 32 |
Sound pressure at 5m | 57 dB(A) |
Transport weight | 2000 kg |
Dimensions (l x w x h) | 4500 x 1460 x 2100 mm |
*(**) Design conditions: | * Design conditions: Hot water temperatures 40/45°, Ambient temperature 7°C |
*** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-200/WP/P - Heat pump air to water 213kW
Product information
Different requirements and applications on request.
Product description:
Air to water heat pump with reversible operation can be used for heating/cooling. The unit is equipped with quiet running scroll compressors. The heat pump has an integrated pump with a head height of 27 m (270 kPa), it should be set up on a horizontal, stable area, and should have at least 1 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
Pumps | |
Heat exchangers | |
Hoses / Fittings | |
Electric Accessories | |
Remote Monitoring |