| *Cooling Capacity | 261 kW |
|---|---|
| Power input | 96 kW |
| Voltage | 400 V / 50 Hz / 3 Phases |
| Operating current | 208 A |
| Electrical connection | Cable terminals 3 Ph + PE |
| ** Fuse protection | 250 A |
| ** Cable recommendation | 4 x 95 (Single wire) mm² |
| Flow rate | 44,8 m³/h |
| Max. operating pressure | 6 bar |
| External pressure head | 17 m |
| Cold water connections | Storz A |
| Capacity control | 4 Steps |
| Refrigerant | R 32 |
| Sound pressure at 5m | 64 dB(A) |
| Transport weight | 2000 kg |
| Dimensions (l x w x h) | 2330 x 2240 x 2760 mm |
| * Design conditions: | Evaporator water temperatures 12/7°, Ambient temperature 35 °C |
| ** Electrical protection: | ** On-Site power installation should be entrusted to an electrical specialist. |
| Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-260/P - Air cooled chiller 261kW
Product information
Different requirements and applications on request.
Product description:
Air cooled corrosion resistant chiller for outdoor locations. This mechanical refrigeration unit for providing cold water is equipped with a very quiet running screw compressor. The liquid cooler has an integrated cold water pump head height of 17 m (170 kPa), it should be set up on a horizontal, stable work area and have at least 1 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
![]() |
Heat exchangers |
![]() |
Buffer Tanks |
![]() |
Hoses / Fittings |
![]() |
Electric Accessories |
![]() |