*Heating capacity | 59 kW |
---|---|
**Cooling Capacity | 59 kW |
Power input | 21,3 kW |
Voltage | 400 V / 50 Hz / 3 Phases |
Operating current | 51,4 A |
Electrical connection | CEE 63A Socket |
*** Fuse protection | 63 A |
*** Cable recommendation | 16 mm² |
Max. flow rate | 10,1 m³/h |
Max. operating pressure | 6 bar |
External pressure head | 32 m |
Cold water connections | Storz C |
Capacity control | 25-100% (FU) |
Refrigerant | R 32 |
Sound pressure at 5m | 56 dB(A) |
Transport weight | 1050 kg |
Dimensions (l x w x h) | 2400 x 1200 x 2120 mm |
*(**) Design conditions: | * Design conditions: Hot water temperatures 40/45°, Ambient temperature 7°C |
*** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-60/WP/P - Heat pump air to water 59kW
Product information
Different requirements and applications on request.
Product description:
Air to water heat pump with reversible operation can be used for heating/cooling. The unit is equipped with quiet running scroll compressors. The heat pump has an integrated pump with a head height of 32 m (320 kPa), it should be set up on a horizontal, stable area, and should have at least 1 m free space to all sides. All controls and regulators are contained within the housing.