| *Heating capacity | 59 kW |
|---|---|
| **Cooling Capacity | 59 kW |
| Power input | 21,3 kW |
| Voltage | 400 V / 50 Hz / 3 Phases |
| Operating current | 51,4 A |
| Electrical connection | CEE 63A Socket |
| *** Fuse protection | 63 A |
| *** Cable recommendation | 16 mm² |
| Max. flow rate | 10,1 m³/h |
| Max. operating pressure | 6 bar |
| External pressure head | 32 m |
| Cold water connections | Storz C |
| Capacity control | 25-100% (FU) |
| Refrigerant | R 32 |
| Sound pressure at 5m | 56 dB(A) |
| Transport weight | 1050 kg |
| Dimensions (l x w x h) | 2400 x 1200 x 2120 mm |
| *(**) Design conditions: | * Design conditions: Hot water temperatures 40/45°, Ambient temperature 7°C |
| *** Electrical protection: | *** On-Site power installation should be entrusted to an electrical specialist. |
| Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-M-60/WP/P - Heat pump air to water 59kW
Product information
Different requirements and applications on request.
Product description:
Air to water heat pump with reversible operation can be used for heating/cooling. The unit is equipped with quiet running scroll compressors. The heat pump has an integrated pump with a head height of 32 m (320 kPa), it should be set up on a horizontal, stable area, and should have at least 1 m free space to all sides. All controls and regulators are contained within the housing.
Accessories (optional)
![]() |
Pumps |
![]() |
Heat exchangers |
![]() |
Hoses / Fittings |
![]() |
Electric Accessories |
![]() |
Remote Monitoring |