    Exchange Capacity

    Cooling: 700 kW / Heating: 3100 kW

    Flow rate primary

    Cooling: 109 m³/h / Heating: 122 m³/h

    Flow rate secondary

    Cooling: 100 m³/h / Heating: 112 m³/h

    Temperature in / out – prim.

    Cooling: 4/10°C / Heating: 90/66°C

    Temperature in / out – sec.

    Cooling: 12/6°C / Heating: 60/84°C

    Pressure drop primary

    Cooling: 50 kPa / Heating: 56 kPa

    Pressure drop secondary

    Cooling: 41 kPa / Heating: 52 kPa

    Medium primary side

    30% Ethylene glycol

    Medium secondary

    Water

    *Water connections

    Storz A

    Filter

    Type KSB DN100

    Transport weight

    1100 kg

    Dimensions (l x w x h)

    2400 x 800 x 2110 mm

    * On request

    Connections individually configurable

    Remarks

    Technical and design changes can be made at any time without prior notice!

    Product description:

    External plate heat exchanger, dirt trap and gate valve mounted on a stable base frame. Extensive accessories are available as options.

    Accessories (optional)

    Pumpenmodul Pumps
    Buffer Tanks Buffer Tanks
    Hoses / Fittings Hoses / Fittings
    Electric Accessories Electric Accessories