ACR-PW-100-108 - Heat exchanger 700/3100kW

Product information


Different requirements and applications on request.

Exchange Capacity

Cooling: 700 kW / Heating: 3100 kW

Flow rate primary

Cooling: 109 m³/h / Heating: 122 m³/h

Flow rate secondary

Cooling: 100 m³/h / Heating: 112 m³/h

Temperature in / out – prim.

Cooling: 4/10°C / Heating: 90/66°C

Temperature in / out – sec.

Cooling: 12/6°C / Heating: 60/84°C

Pressure drop primary

Cooling: 50 kPa / Heating: 56 kPa

Pressure drop secondary

Cooling: 41 kPa / Heating: 52 kPa

Medium primary side

30% Ethylene glycol

Medium secondary

Water

*Water connections

Storz A

Filter

Type KSB DN100

Transport weight

1250 kg

Dimensions (l x w x h)

2500 x 1000 x 2230 mm

* On request

Connections individually configurable

Remarks

Technical and design changes can be made at any time without prior notice!

Product description:

External plate heat exchanger, dirt trap and gate valve mounted on a stable base frame. Extensive accessories are available as options.

Accessories (optional)

Pumpenmodul Pumps
Buffer Tanks Buffer Tanks
Hoses / Fittings Hoses / Fittings
Electric Accessories Electric Accessories

Product request










    Privacy policy*

    You agree to processing of your data to deal with your inquiry. A copy of the message will be sent to your email address.
    (For more information, see our privacy policy)