Exchange Capacity | Cooling: 850 kW / Heating: 3000 kW |
---|---|
Flow rate primary | Cooling: 132 m³/h / Heating: 141 m³/h |
Flow rate secondary | Cooling: 122 m³/h / Heating: 129 m³/h |
Temperature in / out – prim. | Cooling: 4/10°C / Heating: 90/70°C |
Temperature in / out – sec. | Cooling: 12/6°C / Heating: 60/80°C |
Pressure drop primary | Cooling: 49 kPa / Heating: 51 kPa |
Pressure drop secondary | Cooling: 41 kPa / Heating: 47 kPa |
Medium primary side | 30% Ethylene glycol |
Medium secondary | Water |
*Water connections | Storz A |
Filter | Type KSB DN100 |
Transport weight | 900 kg |
Dimensions (l x w x h) | 2300 x 720 x 1710 mm |
* On request | Connections individually configurable |
Remarks | Technical and design changes can be made at any time without prior notice! |
ACR-PW-122-132 - Heat exchanger 850/3000kW

Product information
Different requirements and applications on request.
Product description:
External plate heat exchanger, dirt trap and gate valve mounted on a stable base frame. Extensive accessories are available as options.
Accessories (optional)
![]() |
Pumps |
![]() |
Buffer Tanks |
![]() |
Hoses / Fittings |
![]() |
Electric Accessories |