ACR-PW-14-16 - Heat exchanger 100/1050kW

Product information


Different requirements and applications on request.

Exchange Capacity

Cooling: 100 kW / Heating: 1050 kW

Flow rate primary

Cooling: 15,6 m³/h / Heating: 49,3 m³/h

Flow rate secondary

Cooling: 14,3 m³/h / Heating: 45,1 m³/h

Temperature in / out – prim.

Cooling: 4/10°C / Heating: 90/70°C

Temperature in / out – sec.

Cooling: 12/6°C / Heating: 60/80°C

Pressure drop primary

Cooling: 6 kPa / Heating: 48 kPa

Pressure drop secondary

Cooling: 5 kPa / Heating: 45 kPa

Medium primary side

30% Ethylene glycol

Medium secondary

Water

*Water connections

Storz B

Filter

Type DN50/PN16 KSB

Transport weight

275 kg

Dimensions (l x w x h)

1150 x 700 x 1350 mm

* On request

Connections individually configurable

Remarks

Technical and design changes can be made at any time without prior notice!

Product description:

External plate heat exchanger, dirt trap and gate valve mounted on a stable base frame. Extensive accessories are available as options.

Accessories (optional)

Pumpenmodul Pumps
Buffer Tanks Buffer Tanks
Hoses / Fittings Hoses / Fittings
Electric Accessories Electric Accessories

Product request










    Privacy policy*

    You agree to processing of your data to deal with your inquiry. A copy of the message will be sent to your email address.