ACR-PW-40-44 - Heat exchanger 280/2200kW

Productrequest








    Privacy policy*

    You agree to processing of your data to deal with your inquiry. A copy of the message will be sent to your email address.
    (For more information, see our privacy policy)

    Please prove you are human by selecting the cup.

    Product information


    Different requirements and applications on request.

    Exchange Capacity

    Cooling: 280 kW / Heating: 2200 kW

    Flow rate primary

    Cooling: 44 m³/h / Heating: 103,3 m³/h

    Flow rate secondary

    Cooling: 40 m³/h / Heating: 94,6 m³/h

    Temperature in / out – prim.

    Cooling: 4/10°C / Heating: 90/70°C

    Temperature in / out – sec.

    Cooling: 12/6°C / Heating: 60/80°C

    Pressure drop primary

    Cooling: 11 kPa / Heating: 46 kPa

    Pressure drop secondary

    Cooling: 9 kPa / Heating: 44 kPa

    Medium primary side

    30% Ethylene glycol

    Medium secondary

    Water

    *Water connections

    Storz DM100

    Filter

    Type KSB DN100

    Transport weight

    640 kg

    Dimensions (l x w x h)

    1600 x 700 x 1400 mm

    * On request

    Connections individually configurable

    Remarks

    Technical and design changes can be made at any time without prior notice!

    Product description:

    External plate heat exchanger, dirt trap and gate valve mounted on a stable base frame. Extensive accessories are available as options.

    Accessories (optional)

    Pumpenmodul Pumps
    Buffer Tanks Buffer Tanks
    Hoses / Fittings Hoses / Fittings